NIBCO Rubber-Seated Butterfly Valves User Manual

Page 3

Advertising
background image

NIBCO Technical Services • Phone: 1.888.446.4224 • Fax: 1.888.336.4224

3

relation to the valve body and piping system. Pre-planning may save from having to
remove a “just installed” valve and reinstalling in another orientation.

TABLE 1

Piping/Flange Inside Diameter Requirements

III.

GEAR OPERATOR INSTALLATION HANDWHEEL POSITIONING

TABLE 2

Tools Required

Fire Protection

(UL/FM)

2” – 8”

9/16” hex wrench and 1/8” hex Allen wrench

10” – 12”

3/4” hex wrench and 1/8” hex Allen wrench

Commercial

2” – 8”

9/16” hex wrench

10” – 14”

3/4” hex wrench

16” – 18”

1-1/8” hex wrench



Valve

Series

LD/WD/LC/WC

1000/2000/3000/5000

LD7000/8000 Series

N200 Series

Valve Size

(Inches)

Minimum

Pipe/Flange

ID for Disc

Clearance

Maximum

Pipe/Flange

ID for

Proper Seal

Minimum

Pipe/Flange

ID for Disc

Clearance

Maximum

Pipe/Flange

ID for

Proper Seal

Minimum

Pipe/Flange

ID for Disc

Clearance

Maximum

Pipe/Flange

ID for

Proper Seal

2

2.00

2.49

1.31

2.43

1.38

2.24

2-1/2

2.37

2.86

1.89

3.06

1.95

2.74

3

2.67

3.43

2.64

3.65

2.66

3.33

4

3.69

4.55

3.67

4.75

3.67

4.55

5

4.76

5.62

4.44

5.54

4.48

5.50

6

5.96

6.62

5.96

6.84

5.96

6.66

8

8.01

8.62

7.85

8.89

7.85

8.61

10

10.00

10.80

9.73

10.70

9.76

10.75

12

11.99

13.12

11.71

12.74

11.72

12.79

14

13.16

13.77

13.02

15.50

16

15.34

16.30

15.20

17.90

18

17.23

18.31

17.16

19.67

20

19.04

20.08

19.10

21.05

24

23.05

24.71

23.04

25.57

28

27.10

29.31

30

29.06

30.29

29.08

31.28

32

30.91

33.93

36

33.59

35.78

33.60

36.77

42

39.83

42.77

39.87

44.96

48

44.85

48.27

44.86

51.57

54

50.67

54.25

60

54.93

60.25

Advertising