10

IRON VALVE BOLT TORQUE


Before tightening, make sure all surfaces that the fastener will contact are clean and dry.

The torque tightening table listed below applies to clean, undamaged, non-lubricated threaded
fasteners (lubricated threaded fasteners may require less torque – consult the fastener
manufacturer for more detailed instructions).

When tightening, use the sequence chart below. Tighten in two steps.

1. Tighten fastener using about 1/2 the final torque figure.
2. Final tightening using the full torque figure. ASTM A307 steel only.

Fastener Size

7/16

1/2

9/16

5/8

3/4

7/8

1

1-1/8

1-1/4

1-3/8

1-1/2

Torque in Ft. Lbs.

30

45

66

93

150

202

300

474

659

884

1057

BOLT TIGHTENING SEQUENCE



For any technical enquiries please call NIBCO Technical Services.