6 user defined triggers, User defined triggers, User manual – SurgeX SX-AX20E User Manual

Page 18

Advertising
background image

© 2015 SurgeX/Electronic Systems Protection, Inc. | Technical Support: 800-645-9721 | surgex.com 18

User Manual

Firmware Version v2.04.281

5.5.6 User Defined Triggers

User defined triggers that have previously been
created are displayed in a list. The name of the

trigger is the name that was given to the trigger
when it was created. Pressing “Test Alarm” will

activate the trigger alarm action, and pressing

“Test Clear” will activate the trigger clear action;

use these test functions to verify that the trigger

will operate as intended.

Pressing “Edit” will open the trigger for editing,

and pressing “Delete” will delete the trigger. New
triggers may be created by pressing the “New

Trigger” button

Type

Trigger Executes When:

Trigger Clears When:


Threshold

Temperature High

Temperature > Set Point

Temp < Set - Hysteresis

Temperature Low

Temperature < Set Point

Temp > Set + Hysteresis

Voltage High

Voltage > Set Point

Voltage < Set – Hysteresis

Voltage Low

Voltage < Set Point

Voltage > Set + Hysteresis

Line Current High

Total Current > Set Point

Current < Set – Hysteresis

Line Current Low

Total Current < Set Point

Current > Set + Hysteresis

Outlet Current High

Outlet X Current > Set Point

Current < Set – Hysteresis

Outlet Current Low

Outlet X Current < Set Point

Current > Set + Hysteresis

Net Test

IP Address Ping Fails

IP Address Ping Succeeds

Schedule

Set Date and Time

NA

Contact Closure

Contact Closure Input Closes

Contact Closure Input Opens


Alarm/Clear Actions

Outlet On

Outlet Off

Outlet Reboot

Run Sequence

Email

None