Installation, 120 volt connections, Ethernet connections – SurgeX SX-AX20E User Manual

Page 7: User manual

Advertising
background image

User Manual

Firmware Version v2.04.281

© 2015 SurgeX/Electronic Systems Protection, Inc. | Technical Support: 800-645-9721 | surgex.com 7

Example: Telnet to DHCP-Assigned IP Address 192.168.1.199 on Port 23 and change to Static IP Address 192.168.1.3.

Axess ELITE
Connected to Telnet Session 1

User> admin

Password> *****

Axess ELITE> set ipmode static

OK

Axess ELITE Reboot Required > set ipaddress 192.168.1.3

OK

Axess ELITE Reboot Required> set subnet 255.255.255.0

OK

Axess ELITE Reboot Required> set gateway 192.168.1.7

OK

Axess ELITE Reboot Required> reboot

3.

Installation

The SurgeX Axess Elite is designed to be installed in a 19 inch equipment rack and requires one unit (1-U) of rack space.

Use the four screws provided with the product to secure the rack ears to the rack rails. These screws can be tightened by

hand and do not require tools. Connect power to the unit by plugging the cord into a 120V AC, 15 (20) amp wall or floor
receptacle. Do not plug the unit into a relocatable power tap.

3.1

120 Volt Connections

The Axess Elite has a total of 8 receptacles. Each receptacle is rated for a maximum load of 15 amps, but the

total load of the Axess Elite must not exceed 15 (20) amps. Plug the equipment cords into the receptacles as
needed. The receptacles are numbered 1 through 8. This same numbering is used in the control interface.

3.2

Ethernet Connection

The RJ45 connector for Ethernet is situated on the rear panel beside the Serial connector. The default IP Address

is 192.168.1.199.

3.3

RS232 (Serial) Port Connection

The Axess Elite has a 9 pin D subminiature connector for RS-232 serial control. The connector is configured as
DCE for direct connection to a laptop or other terminal device. Default serial parameters are 115,200 bps, 8 data,

no parity, 1 stop bit (9600,8,n,1).

Advertising
This manual is related to the following products: