INSTALLATION AND CLEARANCES
(Vent-Free Operation Only)

WARNING: Maintain the

minimum clearances. If you can,

provide greater clearances from

floor, ceiling and adjoining wall.

Minimum Fireplace Clearance to

Combustible Materials

Side Wall 16", Ceiling 42", Front 36"

Minimum Firebox Size

Height 17", Depth 14", Front Width 24",

Rear Width 20" (measured at 14" depth).

Carefully follow instructions below. This
will ensure safe installation into a masonry,
UL127-listed manufactured fireplace or certi-
fied vent-free firebox.

Minimum Clearances For Side
Combustible Material, Side Wall and
Ceiling
A. Clearances from side of fireplace cabinet

to any combustible material and wall
should follow diagram in Figure 4.

Example: The face of a mantel, bookshelf,
etc. is made of combustible material and
protrudes 3

1

/

2

" from the wall. This com-

bustible material must be 4" from the side
of the fireplace cabinet (see Figure 4).

Note: When installing your gas logs into
a manufactured firebox, follow firebox
manufacturer’s instructions for minimum
clearances to combustible materials.

B. Clearances from the top of the fireplace

opening to the ceiling should not be less
than 42".

Figure 4 - Minimum Clearance for

Combustible to Wall

*Minimum 16" from Side Wall

*

Example

INSTALLATION

Continued

NOTICE: Manual control heaters

may be used as a vented product.

If so, you must always run heater

with chimney flue damper open. If

running heater with damper open,

noncombustible material above fire-

place opening is not needed. Go to

Installing Damper Clamp Accessory

for Vented Operation, page 11.

Minimum Noncombustible Material
Clearances

If Not Using Mantel

Note: If using a mantel, proceed to If Using
Mantel, page 10. If not using a mantel, follow
the information below.
You must have noncombustible material(s)
above the fireplace opening. Noncombustible
materials (such as slate, marble, tile, etc.) must
be at least 1/2" thick. With sheet metal, you
must have noncombustible material behind it.
Noncombustible material must extend at least 8"
up. See Figure 5 for minimum clearances.

Noncombustible
Material

Requirements for

Distance (A)

Safe Installation

12" or more

Noncombustible material okay.

Between 8" and 12" Noncombustible material okay.
Less than 8"

Noncombustible material must

be extended to at least 8".

See Between 8" and 12",

above. If you cannot extend

material, you must operate

heater with flue damper open.

Heat Resistant
Material

(A)

Figure 5 - Heat Resistant Material (Slate,

Marble, Tile, etc.) Above Fireplace