Operating parameters cont, Dual capacity models, Envision – WaterFurnace Envision2 User Manual

Page 43: Compact - 50 hz installation manual, First stage operation, Second stage operation

Advertising
background image

43

ENVISION

2

COMPACT - 50 HZ INSTALLATION MANUAL

Operating Parameters cont.

Dual Capacity Models

First Stage Operation

Entering Water

Temp °C

Water Flow

L/s per kW

Cooling -- No Hot Water Generation

Suction Pressure

kPa

Discharge

Pressure kPa

Superheat

Subcooling

Water Temp Rise

°C

Air Temp Drop

°C DB

-1.1

0.09

724 - 827

965 - 1069

11 - 19

5 - 9

6 - 11

9 - 13

0.19

689 - 793

793 - 896

11 - 19

5 - 9

4 - 7

9 - 13

10

0.09

862 - 965

1413 - 1551

7 - 11

4 - 8

6 - 11

9 - 13

0.19

827 - 931

1241 - 1379

7 - 11

4 - 8

4 - 7

9 - 13

21.1

0.09

931 - 1000

1931 - 1999

6 - 9

4 - 8

9- 11

9 - 13

0.19

917 - 986

1724 - 1793

6 - 9

4 - 8

5 - 7

9 - 13

32.2

0.09

979 - 1048

2378 - 2448

4 - 7

4 - 8

8 - 11

9 - 13

0.19

965 - 1034

2275 - 2344

4 - 7

4 - 8

4 - 7

9 - 13

43.3

0.09

1048 - 1089

2792 - 2999

4 - 7

4 - 8

8 - 11

9 - 13

0.19

1020 - 1055

2689 - 2896

4 - 7

4 - 8

4 - 7

9 - 13

Entering Water

Temp °C

Water Flow

L/s per kW

Heating -- No Hot Water Generation

Suction Pressure

kPa

Discharge

Pressure kPa

Superheat

Subcooling

Water Temp Drop

°C

Air Temp Rise

°C DB

-1.1

0.09

524 - 579

1862- 1965

4 - 7

2 - 6

3 - 5

7 - 9

0.19

552 - 607

1896 - 1999

4 - 7

2 - 6

2 - 4

8 - 10

10

0.09

689- 793

1931 - 2137

6 - 8

2 - 6

4 - 6

10 - 12

0.19

724 - 827

1999- 2172

6 - 8

2 - 6

3 - 5

11 - 13

21.1

0.09

931- 1034

2137 - 2241

7 - 9

2 - 6

4 - 7

13 - 16

0.19

965- 1069

2172 - 2275

7 - 9

2 - 6

3 - 6

12 - 17

32.2

0.09

1069 - 1138

2275 - 2551

7 - 9

2 - 6

4 - 7

13 - 16

0.19

1103 - 1172

2344 - 2620

7 - 9

2 - 6

3 - 6

12 - 17

43.3

0.09

0.19

NOTE: Cooling performance based on entering air temperatures of 26.7°C DB, 67°C WB.

Heating performance based on entering air temperature of 21.1°C DB.

6/25/12

Second Stage Operation

Entering Water

Temp °C

Water Flow

L/s per kW

Cooling -- No Hot Water Generation

Suction Pressure

kPa

Discharge

Pressure kPa

Superheat

Subcooling

Water Temp Rise

°C

Air Temp Drop

°C DB

-1.1

0.09

793 - 862

1034 - 1172

11 - 19

6 - 9

6 - 11

5 - 7

0.19

724 - 827

896 - 1000

11 - 19

6 - 9

4 - 6

9 - 13

10

0.09

896 - 965

1482 - 1620

7 - 11

4 - 8

9 - 11

9 - 13

0.19

883 - 951

1310 - 1448

7 - 11

4 - 8

4 - 7

9 - 13

21.1

0.09

951 - 1020

1931 - 2137

6 - 9

6 - 9

8 - 12

9 - 13

0.19

938 - 1007

1724 - 1931

6 - 9

4 - 8

4 - 7

9 - 13

32.2

0.09

1000 - 1069

2413 - 2620

5 - 8

6 - 9

8 - 11

9 - 13

0.19

986 - 1055

2206- 2413

5 - 8

4 - 8

3 - 6

9 - 13

43.3

0.09

1000 - 1069

2896 - 3103

5 - 8

6 - 9

8 - 11

9 - 13

0.19

986 - 1055

2792 - 2999

5 - 8

4 - 8

3 - 6

9 - 13

Entering Water

Temp °C

Water Flow

L/s per kW

Heating -- No Hot Water Generation

Suction Pressure

kPa

Discharge

Pressure kPa

Superheat

Subcooling

Water Temp Drop

°C

Air Temp Rise

°C DB

-1.1

0.09

503 - 586

1862 - 2103

4 - 8

2 - 6

3 - 6

8 - 12

0.19

531 - 621

1931 - 2172

4 - 8

2 - 6

2 - 4

9 - 13

10

0.09

669 - 758

1999 - 2241

6 - 9

2 - 6

5 - 7

12 - 16

0.19

703 - 793

2068 - 2310

6 - 9

2 - 6

4 - 6

13- 17

21.1

0.09

896 - 1000

2206 - 2448

7 - 11

2 - 6

6 - 8

17 - 20

0.19

931 - 1034

2241 - 2482

7 - 11

2 - 6

4 - 7

17 - 21

32.2

0.09

1034 - 1103

2413 - 2689

7 - 11

2 - 6

6 - 8

17 - 20

0.19

1069 - 1138

2517 - 2792

7 - 11

2 - 6

4 - 7

17 - 21

43.3

0.09

0.19

NOTE: Cooling performance based on entering air temperatures of 26.7°C DB, 67°C WB.

Heating performance based on entering air temperature of 21.1°C DB.

6/25/12

Advertising