Horizontal dimensional data cont, Horizontal disconnect, Envision – WaterFurnace Envision2 User Manual

Page 9: Compact - 50 hz installation manual

Advertising
background image

9

ENVISION

2

COMPACT - 50 HZ INSTALLATION MANUAL

2.1 in.

[5.3 cm]

KK

Disconnect Located

on this Side for a

Left Return

Disconnect
Location

Power Supply

Horizontal Shown in

Right Return Configuration

Horizontal Models

KK

005

23.4

006

23.4

009

28.4

012

25.9

015

28.4

017

25.9

Dimensions in cm

6/25/12

Horizontal Disconnect

When using disconnect, do not use dimension K from the

standard horizontal dimensional data. Use dimension KK

from the horizontal disconnect dimensional data.

Horizontal

Models

Overall Cabinet

Water Connections

Electrical Knockouts

1

2

3

Loop

Water FPT

J

K

A

B

C

D

E

H

12.7 mm cond

25.4 mm

Width

Depth

Height*

In

Out

Condensate

Low Voltage

Power Supply

005

cm

57.2

106.7

48.8

4.6

17.3

2.0

19.05 mm

23.1

18.0

006

cm

57.2

114.3

48.8

4.6

17.3

2.0

19.05 mm

23.4

18.0

009

cm

64.8

121.9

53.8

4.6

17.3

2.0

25.4 mm

23.4

23.1

012

cm

64.8

134.6

53.8

4.6

17.3

2.0

25.4 mm

23.4

23.1

015

cm

64.8

154.9

53.8

4.6

17.3

2.0

25.4 mm

23.4

23.1

017

cm

64.8

172.7

53.8

4.6

17.3

2.0

25.4 mm

23.4

23.1

6/25/12

Horizontal

Models

Discharge Connection

duct flange installed (

±2.54mm)

Return Connection

using deluxe filter rack option (

±2.54 mm)

Unit Hanger Dimensions

PVC Size

L

M

N

P

Q

R

S

T

U

V

W

X

Supply

Width

Supply

Depth

Return

Depth

Return
Height

005

cm

17.0

26.7

23.9

12.4

69.6

42.2

5.1

3.6

108.6

63.8

54.4

1.9

006

cm

17.0

26.7

23.9

12.4

77.2

42.2

5.1

3.8

116.3

63.8

54.4

1.9

009

cm

12.4

34.5

33.5

11.7

89.9

47.2

5.8

3.6

124.0

71.4

62.0

1.9

012

cm

12.4

34.5

33.5

11.7

102.6

47.2

5.8

3.6

136.7

71.4

62.0

1.9

015

cm

12.4

34.5

33.5

11.7

115.3

47.2

5.8

3.6

157.0

71.4

62.0

1.9

017

cm

12.4

34.5

33.5

11.7

115.3

47.2

5.8

3.6

174.8

71.4

62.0

1.9

Horizontal units shipped with standard 50.8 mm (field adjustable to 25.4mm) open application filter rack extending 55.88 mm from
unit and is not suitable for duct connection. For ductable return connection applications, order the deluxe 50.8 mm (field adjustable
to 25.4 mm) duct collar/filter rack which extends 82.55 mm from the unit and is suitable for duct connections.

6/25/12

Horizontal Dimensional Data cont.