Electrical data, Clw quad series chiller installation manual – WaterFurnace CLW Chiller User Manual

Page 11

Advertising
background image

11

CLW QUAD SERIES CHILLER INSTALLATION MANUAL

Electrical Data

MCA (Maximum Current Rating) is a calculation based off the RLA of the compressor on the electrical connection
and is used to properly size the wire. Please refer to NEC for additional information.

MOCP (Maximum Over Current Protection) is a calculation based off the RLA of the compressor on the electrical
connection and is used to fuses and breakers. Please refer to NEC for additional information.

Notes:
1.

Where RLA1 is equal to the largest compressor in the system and the others RLA's are all subsequent
motors present in the system.

2.

Total unit MCA shall not exceed 500A or a second connection will be required.

Model

Rated

Voltage

Voltage

Min/Max

HP

Compressor

Unit

MCC

RLA1

MOA

MCA

HP

MOCP

060

208-230/60/3

187/253

15

89.9

57.6

77.3

244.8

60

302.4

460/60/3

414/506

43.0

27.6

35.0

117.3

144.9

575/60/3

517/633

34.4

22.0

28.0

93.5

115.5

080

208-230/60/3

187/253

20

110.7

70.9

108.0

301.3

80

372.2

460/60/3

414/506

54.1

34.7

48.8

147.5

182.2

575/60/3

517/633

43.3

27.8

39.1

118.2

146.0

100

208-230/60/3

187/253

25

132.8

85.1

117.7

361.7

100

446.8

460/60/3

414/506

63.5

40.7

53.2

173.0

213.7

575/60/3

517/633

50.8

32.6

42.6

138.6

171.2

120

208-230/60/3

187/253

30

165.6

106.2

145.1

451.4

120

557.6

460/60/3

414/506

82.8

53.1

65.6

225.7

278.8

575/60/3

517/633

66.3

42.5

52.5

180.6

223.1

140

208-230/60/3

187/253

35

160.4

102.8

165.8

436.9

140

539.7

460/60/3

414/506

80.2

51.4

75.0

218.5

269.9

575/60/3

517/633

64.2

41.1

60.0

174.7

215.8