CLW QUAD SERIES CHILLER INSTALLATION MANUAL

Heat of Extraction Data

Model

Source

GPM

Load

GPM

EST

Heat Of Extraction (HE)

ºF

105°F

110°F

115°F

120°F

125°F

060

180

180

50

864.6

847.6

837.4

827.6

823.8

55

920.0

910.6

901.2

889.2

877.4

60

992.4

978.4

962.6

955.6

941.6

65

1062.0

1046.0

1035.8

1021.0

1003.2

080

240

240

50

1145.4

1129.0

1116.4

1111.4

1098.4

55

1226.4

1219.6

1201.6

1185.4

1169.8

60

1323.0

1304.2

1283.4

1276.2

1255.2

65

1426.8

1405.0

1380.8

1361.6

1337.6

100

300

300

50

1366.0

1360.6

1343.2

1329.0

1312.4

55

1462.6

1455.4

1436.8

1418.4

1398.2

60

1577.8

1556.4

1546.0

1524.8

1503.2

65

1701.0

1676.4

1664.0

1639.0

1613.8

120

360

360

50

1762.6

1743.6

1723.0

1700.8

1693.8

55

1892.0

1867.4

1857.4

1833.2

1807.2

60

2043.6

2014.8

1986.6

1973.6

1945.8

65

2189.2

2156.8

2140.8

2108.6

2076.8

140

420

420

50

1937.4

1910.0

1885.8

1876.0

1850.0

55

2077.2

2065.0

2033.2

2004.8

1974.2

60

2244.2

2211.6

2179.0

2159.2

2126.4

65

2405.0

2387.0

2349.6

2312.0

2287.6