CLW QUAD SERIES CHILLER INSTALLATION MANUAL

Control Features

Alarm Outputs

•

The control has 18-enumerated status variable for each

compressor and the unit.

• Compressor

Lockout

•

Any compressor can be locked out from the local

display or using the HOA switch.

Motor & Oil Thermal Overload

•

The motor thermal overload switch is a normally

closed (NC) switch that monitors the temperature of

the motor.

•

This safety can be configured to auto reset or manual

reset (factory default).

Motor Rotation Direction

•

The motor rotation direction switch is a normally

closed (NC) switch that monitors the rotation direction

of the motor.

Electrical Thermal Overload

•

The electrical thermal overload switch is a normally

closed (NC) switch that monitors the electrical thermal

conditions of the wires leaving the main contactor.

•

This safety can be configured to auto reset or manual

reset (factor default).

Flow Switches

•

The optional flow switches are normally closed (NC)

switch that monitors the flow in the pipes into the

evaporator and condenser.

•

This safety clears when flow is present.

Freeze Protection

•

The optional freeze protection switch is a normally

closed (NC) switch that monitors the temperature of

the water in the pipe coming out of the evaporator for

freeze conditions.

•

This safety can be configured to auto reset or

manual reset.

Low Refrigerant Saturation Temperatures

•

The controller monitors the refrigerant saturation

temperatures for low saturation temperatures. Without

glycol, it is recommend to set the low saturation

temperature to 34°F and consider it an alarm condition

it the saturation temperature continuously remains

below that temperature for 90 seconds.

•

The compressor will not restart until the low saturation

compressor delay time delay has been satisfied.

High Refrigerant Saturation Temperatures

•

The controller monitors the refrigerant saturation

temperatures for high saturation temperatures. An

alarm condition occurs if the saturation temperature

exceeds the high limit.

•

The compressor will not restart until the high saturation

compressor delay time delay has been satisfied.