Direct-vent fireplace, Venting installation, Continued – Desa DVFE34 User Manual

Page 10

Advertising
background image

10

107205

DIRECT-VENT FIREPLACE

For more information, visit www.desatech.com

VENTING
INSTALLATION

Continued

UP

UP

Rigid Vent Pipe

Horizontal Venting

Vertical (V)

Horizontal (H)

37" min.

10" max.

Figure 16 - Horizontal Termination Configuration for Rigid Venting

Figure 17 - Horizontal Termination Configuration for Rigid Venting Using One
90

°

Elbow

Flexible Vent Pipe

Horizontal Venting

Vertical (V)

Horizontal (H)

44" min.

29" max.

(30

°

and 90

°

only, no vertical pipe)

55" min.

41" max.

(30

°

elbow, 1' vertical pipe, 90

°

elbow)

67" min.

60" max.

79" min.

84" max.

96" min.

20' max.

Note: This configuration for use with
corner installation.

Rigid Vent Pipe Horizontal
Termination Configurations

Figures 16 through 19 show different con-
figurations for venting with horizontal ter-
mination. Each figure includes a chart with
vertical minimum/maximum and horizon-
tal maximum dimensions which must be
met. Seal all connections with high tem-
perature silicone sealant (outer pipe only) as
specified in the second warning statement
on page 7. All horizontal terminations re-
quire 1/4" rise per 12" of horizontal run.

FD60
60˚ Starter/
Adapter Required

FD30
30˚ Starter/
Adapter Required

*

*

* Note: Remember to add 1/
4” rise per 12” horizontal
length of pipe.