Venting installation instructions – Desa CGCDV42PR EN User Manual

Page 15

Advertising
background image

www.desatech.com

116236-01G

15

INSTALLATION FOR vERTICAL
TERMINATION

Note:

Vertical restrictor must be installed in all

vertical installations.

1. Determine the route your vertical venting

will take. If ceiling joists, roof rafters or other

framing will obstruct the venting system,

consider an offset (see Figure 19) to avoid cut-

ting load bearing members. Note: Pay special

attention to these installation instructions for

required clearances (air space) to combustibles

when passing through ceilings, walls, roofs,

enclosures, attic rafters, etc. Do not pack air

spaces with insulation. Also note maximum

vertical rise of the venting system and any

maximum horizontal offset limitations.

2. Set the fireplace in desired location. Drop a

plumb line down from the ceiling to the posi-

tion of the fireplace exit flue. Mark the center

point where the vent will penetrate the ceiling.

Drill a small locating hole at this point.

Drop a plumb line from the inside of the roof

to the locating hole in the ceiling. Mark the

center point where the vent will penetrate the

roof. Drill a small locating hole at this point.

Flat Ceiling Installation

1. Cut a 10

3

/

4

" square hole in the ceiling us-

ing the locating hole as a center point. The

opening should be framed to 10

3

/

4

" x 10

3

/

4

"

(273 mm x 273 mm) inside dimensions, as

shown in Figure 9 on page 10 using framing

lumber the same size as the ceiling joists. If

the area above the ceiling is an insulated ceil-

ing or and attic space, nail firestop from the

top side. This prevents loose insulation from

falling into the required clearance space. If the

area above the ceiling is a living space, install

firestop below the framed hole. The firestop

should be installed with no less than three nails

per side (see Figure 20).

2. Assemble the desired lengths of pipe and

elbows necessary to reach from the fireplace

flue up through the firestop. Be sure all pipe

and elbow connections are fully twist-locked

(see Figure 8, page 10).

3. Cut a hole in the roof using the locating hole

as a center point. (Cover any exposed open

vent pipes before cutting hole in roof.) The

10

3

/

4

" x 10

3

/

4

" hole must be measured on

the horizontal; actual length may be larger

depending on the pitch of the roof. There

must be a 1" clearance from the vent pipe to

combustible materials. Frame the opening as

shown in Figure 9, page 10.

4. Connect a section of pipe and extend up

through the hole.

Note: If an offset is needed to avoid obstruc-

tions, you must support the vent pipe every 3

feet. Use wall straps for this purpose (see Fig-

ure 19). Whenever possible, use 45° elbows

instead of 90° elbows. The 45° elbow offers

less restriction to the flow of the flue gases

and intake air.

VENTING INSTALLATION

INSTRUCTIONS

Continued

Figure 19 - Offset with Wall Strap and 45°

Elbows

45° Elbow

Wall Strap

Roof
Flashing

Figure 20 - Installing Firestop

If area above is a living space, install

firestop below framed hole.

If area above is an attic space or insulated

area, install firestop above framed hole.

Ceiling Firestop

Advertising
This manual is related to the following products: