1 safety characteristic data, Safety characteristic data – Pilz PNOZ m EF 8DI4DO User Manual
Page 19

Technical details
Operating Manual PNOZ m EF 8DI4DO
1002661EN02
19
8.1
Safety characteristic data
Unit
Operating
mode
EN ISO
138491: 2008
PL
EN ISO
138491: 2008
Category
EN IEC 62061
SIL CL
EN IEC 62061
PFH
D
[1/h]
EN ISO
138491: 2008
T
M
[year]
Logic
CPU
–
PL e
Cat. 4
SIL CL 3
2,84E10
20
Input
SC inputs
1channel
PL d
Cat. 2
SIL CL 2
2,10E09
20
SC inputs
2channel
PL e
Cat. 4
SIL CL 3
4,27E11
20
SC inputs
1ch., pulsed
light barrier
PL e
Cat. 4
SIL CL 3
2,10E10
20
Output
SC outputs
1channel
with ad
vanced fault
detection
PL e
Cat. 4
SIL CL 3
2,12E11
20
SC outputs
1channel
PL d
Cat. 2
SIL CL 2
2,29E10
20
SC outputs
2channel
PL e
Cat. 4
SIL CL 3
1,64E10
20
All the units used within a safety function must be considered when calculating the safety
characteristic data.
INFORMATION
A safety function's SIL/PL values are not identical to the SIL/PL values of
the units that are used and may be different. We recommend that you use
the PAScal software tool to calculate the safety function's SIL/PL values.