2 configuration in a browser – Pilz PSSu H PLC1 FS SN SD User Manual

Page 25

Advertising
background image

Pilz GmbH & Co. KG, Felix-Wankel-Straße 2, 73760 Ostfildern, Germany
Telephone: +49 711 3409-0, Telefax: +49 711 3409-133, E-Mail: [email protected]

4-13

4.2

Configuration in a browser

4

Configure PSS 4000 Diag Control

Example

The last two columns should not be used.

Correct configuration:

– "RmdCol1" VALUE="Responsibility"

– "RmdCol2" VALUE="Description"

– "RmdCol3" VALUE="Location.Device"

– "RmdCol4" VALUE="Location.EquipmentID"

– "RmdCol5" VALUE="Location.Address"

– "RmdCol6" VALUE="Deactivated"

– "RmdCol7" VALUE="Deactivated"

Incorrect configuration:

– "RmdCol1" VALUE="Responsibility"

– "RmdCol2" VALUE="Description"

– "RmdCol3" VALUE="Deactivated"

– "RmdCol4" VALUE="Deactivated"

– "RmdCol5" VALUE="Location.Device"

– "RmdCol6" VALUE="Location.EquipmentID"

– "RmdCol7" VALUE="Location.Address"