Pilz PSSu E F 4DO 0.5 User Manual

Page 36

Advertising
background image

Technical details

Operating Manual PSSu E F 4DO 0.5(­T)(­R)
21316­EN­05

36

Environmental data

312210

314210

315210

Climatic suitability

In accordance with the
standard

EN 60068­2­30, EN
60068­2­78

EN 60068­2­30, EN
60068­2­78

–

Humidity

93 % r. h. at 40 °C

93 % r. h. at 40 °C

–

Condensation during op­
eration

Not permitted

Short­term

–

EMC

EN 61000­4­2, EN
61000­4­3, EN 61000­4­4,
EN 61000­4­5, EN
61000­4­6, EN 61000­6­2,
EN 61000­6­4

EN 61000­4­2, EN
61000­4­3, EN 61000­4­4,
EN 61000­4­5, EN
61000­4­6, EN 61000­6­2,
EN 61000­6­4

EN 61000­4­2, EN
61000­4­3, EN 61000­4­4,
EN 61000­4­5, EN
61000­4­6, EN 61000­6­2,
EN 61000­6­4

Vibration

In accordance with the
standard

EN 60068­2­6

EN 60068­2­6

EN 50125­3

Frequency

10,0 ­ 150,0 Hz

10,0 ­ 150,0 Hz

5,0 ­ 2000,0 Hz

Amplitude

0,35 mm

0,35 mm

–

Acceleration

1g

1g

0,23 g

Broadband noise

In accordance with the
standard

–

EN 60068­2­64

EN 61373

Frequency

–

5 ­ 500 Hz

5 ­ 150 Hz

Acceleration

–

1,9grms

0,79 g RMS

Shock stress

In accordance with the
standard

EN 60068­2­27

EN 60068­2­27

EN 50125­3

Acceleration

15g

15g

2g

Duration

11 ms

11 ms

11 ms

In accordance with the
standard

EN 60068­2­29

EN 60068­2­29

EN 61373

Acceleration

10g

10g

5g

Duration

16 ms

16 ms

30 ms

Supply interruptions

In accordance with the
standard

–

–

EN 50155

Class

–

–

S2, C1, C2

Max. operating height
above sea level

2000 m

5000 m

2000 m

Airgap creepage

In accordance with the
standard

EN 60664­1

EN 60664­1

EN 50124­1

Overvoltage category

II

II

OV2

Pollution degree

2

2

PD1

Advertising