2 install compact module, Install compact module – Pilz PSSu K F FCU User Manual
Page 22

Installation
Operating Manual PSSu K F FCU
1002391-EN-04
22
Module with connector and labelling bracket:
76,7 mm
(3.020")
56 mm
(2.205")
128,9 mm
(5.075")
Install compact module
Prerequisite:
}
The head module must be installed.
}
If the head module does not have an integrated power supply, a supply voltage module
must be installed to the right of the head module.
}
A base module with screw terminals may not be installed to the left of the compact
module.
Please note:
}
All contacts should be protected from contamination.
}
The mechanics of the compact modules are designed for 50 plug in/out cycles.
Procedure:
}
Slot the groove on the compact module on to the mounting rail from below [1].
}
Push the compact module back as far as it will go [2].
}
Make sure that the locking mechanism [3] is pushed downwards, connecting the mod-
ule firmly to the mounting rail.
}
On the mounting rail, slide the compact module to the left.
5.2