Wiring

Operating Manual PSSu K F FCU
1002391-EN-04

27

Wiring

General wiring guidelines

Please note:

}

Signal lines do not have to be shielded.

}

The outputs do not need suppression for inductive loads.

}

Use copper wiring.

Connectors' mechanical connection

Please note:

}

The conductor cross section on the spring-loaded terminals without ferrules is 0,20 -

1,00 mm², 22 - 18 AWG.

}

If you are using multi-core or fine-core cables we recommend ferrules in accordance

with DIN 46228/Part 1 or DIN 46228/Part 4, 0.2 ... 1 mm

2

. To crimp the ferrules we rec-

ommend crimping pliers (crimp form A) conforming to EN 60947-1, such as the PZ 6/5
from Weidmüller, for example.

}

Terminal points per connection: 1

}

Stripping length: 8 mm