Install a terminating plate, 5installation, 3 install a terminating plate – Pilz PSSu XR F -T User Manual
Page 17

Pilz GmbH & Co. KG, Felix-Wankel-Straße 2, 73760 Ostfildern, Germany
Telephone: +49 711 3409-0, Telefax: +49 711 3409-133, E-Mail: [email protected]
5-3
5.3
Install a terminating plate
5
Installation
5.3
Install a terminating plate
5300
Install a terminating plate
5-
][Montage XB/XR Abschlussplatte
You will need two different terminating plates for installation:
PSSu A EC XB
– is supplied with the remote module.
– The base system is terminated using the terminating plate
PSSu A EC XB.
PSSu A EC(-T)
– is supplied with the PSSu head modules.
– The remote system is terminated using the terminating plate
PSSu A EC.
INFORMATION
If the base system is accidentally terminated using the terminat-
ing plate PSSu A EC, the I/O modules in the remote system will
not be recognised and will not appear in the process image.
Head module (FS/ST)
I/O module (FS/ST)
I/O module (FS/ST)
I/O module (FS/ST)
I/O module (FS/ST)
Base station
Supply
I/O module (FS/ST)
Remote station
Supply
I/O module (FS/ST)
I/O module (FS/ST)
Base system
Remote system
Terminating plate
PSSu A EC XB
Terminating plate
PSSu A EC
Cable