Wiring, 6interfaces and wiring, 2 wiring – Pilz PSSu XR F -T User Manual
Page 20

6.2
Wiring
6
Interfaces and wiring
Pilz GmbH & Co. KG, Felix-Wankel-Straße 2, 73760 Ostfildern, Germany
Telephone: +49 711 3409-0, Telefax: +49 711 3409-133, E-Mail: [email protected]
6-2
6.2
Wiring
6200
Wiring
6-
][Verdrahtung BA Einleitung
Please note:
][Verdrahtung XB/XR
The connection cable PSSu A RJ45-CAB 1.5M is available as an ac-
cessory.
The base station and remote station must be in the same control cab-
inet.
][Verdrahtung XR BA_Zusatz
The C-rail supply and the periphery supply are not transferred via the ca-
ble connection, so the remote system forms a new supply group.
WARNING!
Risk of electrocution!
Always connect the mounting rail to the protective earth via an
earthing terminal. This will be used to dissipate hazardous volt-
ages in the case of a fault.
If voltages higher than 50 VAC or 120 VDC are connected to the
PSSuniversal, e.g. to switch contacts on relay modules, please
note the following:
– Specific accident prevention regulations apply.
– The C-rail of the supply group should only be connected to
the protective earth (PE).