Technical details – Pilz PSS67 F 16DI SB-T User Manual
Page 47

10-1
Operating Manual: PSS67 F 16DI SB-T
Technical Details
Electrical data
Supply voltage
24 VDC
Voltage tolerance
-15 %/+20 %
Residual ripple DC
5%
Current consumption
90 mA plus load currents taken from the
test pulse outputs
Galvanic isolation
Yes, between inputs and
SafetyBUS p
Connection
B-coded M12 connector
SafetyBUS p
Transmission rate
Max. 500 kBit/s
Cable runs
Max. 3500 m
Transmission type
Differential two-wire cable
Connection
A-coded M12 connector
Digital inputs
Number of inputs
16
Type according to 61101-2
24 VDC Type 1
Separation of supply
Yes, between inputs and SafetyBUS p
“1” Signal
+15 ... +30 VDC
“0” Signal
-3 ... +5 VDC
Input current
Typ. 3.5 mA
Input delay
< 1 ms
Pulse suppression
< 300 µs
Status indicator
Green LED
Dedicated test pulses
Number
4 (configurable in pairs as test pulse or
24 VDC output)
Output current at “1” signal
Max. 0.125 A per pin
Total load capacity
Max. 0.25 A per test pulse group
Cable runs
Between test pulse output and input
Max. 100 m