Table 7. Settings (continued)

Description

Default Setting

Available Settings

Qualify Bypass

[Always] [Never] [Bypass Disabled]

If Always, Bypass operation is allowed when:

S Bypass voltages > the value set for Bypass

Voltage Low Limit

S Bypass voltages < the value set for Bypass

Voltage High Limit

S Bypass frequency > (nominal frequency -3 Hz)
S Bypass frequency < (nominal frequency +3 Hz)
S Inverter is synchronized with Bypass when

unsynchronized transfers are disabled by the
value set for Unsynchronized Transfers

If Never, Bypass operation is always allowed; voltage
and frequency limits are not in use.

If Bypass Disabled, Bypass operation is prohibited.

Always

Synchronization Window

[Sync Disabled] [±0.5 Hz] [±1.0 Hz] [±1.5 Hz]
[±2.0 Hz] [±2.5 Hz] [±3.0 Hz]

If ±3.0 Hz, on inverter operation the inverter tries to
synchronize with the Bypass when the Bypass
frequency is not more than 3 Hz from the nominal
output frequency; otherwise, the inverter goes to
nominal frequency. On Bypass mode, the sync
window is always ±3 Hz.

NOTE:

In Sync Disabled state, if the Bypass

operation is allowed, the UPS synchronizes only
when it is operating on Bypass mode.

±

3.0 Hz

Unsynchronized Transfers

[Enabled] [Disabled]

If Enabled, unsynchronized transfers to the Bypass
are allowed.

If Disabled, unsynchronized transfers to the Bypass
are not allowed.

NOTE:

The Qualify Bypass setting may overrule the

Unsynchronized Transfers setting.

Enabled

External Battery Module (EBM)

[0] [1]

See “Configuring the UPS for an EBM” on page 52.

0