Dell H967N User Manual

Page 65

Advertising
background image

65

Specifications

|

Table 15. Battery

Configuration

UPS: (8) 12V, 9 Ah internal batteries; EBM: (16) 12V, 9 Ah batteries

Voltage

96 Vdc internal, 96 Vdc EBM

Fuses

UPS: (2) 30A fast fuses in parallel

EBM: Fuse(s)

Type

Sealed, maintenance‐free, valve‐regulated, lead‐acid

Charging

Internal battery: Approximately 4 hours to 90% charge from a UPS/battery discharge

of 50% rated load

EBM: Approximately 12 hours to 90% charge from a UPS/battery discharge of 50%

rated load

Monitoring

Advanced monitoring for earlier failure detection and warning

Battery Runtimes*

Internal batteries: 5 minutes at full load/15 minutes at half load

UPS with one EBM attached: 22 minutes at full load/46 minutes at half load

*Battery runtimes are approximate and vary depending on the load configuration and battery charge.

Battery

DC/DC

Input
Filter

Output

Filter

Bypass

Charger

DC/AC

Inverter

AC/DC

Boost

Figure 27. Online UPS Block Diagram