Dell H967N User Manual

Page 64

Advertising
background image

64

|

Specifications

Table 13. Electrical Output

120V Models

208V Models

230V Models

Power Levels
(rated at nominal inputs)

2700W

Regulation (Normal mode)

-6% to +6% of nominal voltage

NOTE:

This varies based on auto-detected input voltage or customer settings.

Regulation (Battery mode),
Nominal Voltage ±5%

-6% to +6% of nominal voltage

NOTE:

This varies based on auto-detected input voltage or customer settings.

Voltage Waveform

Sine wave

Output Receptacles

(1) L5-20R, 20A

(2) 5-20R, 20A

(2) IEC 320-C13, 15A

(1) L6-20R, 20A

(2) L6-30R, 30A

(6) IEC 320-C13, 10A

(1) IEC 320-C19, 16A

(2) IEC 320-C13, 10A

Table 14. Environmental and Safety

120V Models

208V Models

230V Models

Operating Temperature

Up to 1,500 meters: 0°C to 40°C (32°F to 104°F)

Above 1,500 meters: 0°C to 35°C (32°F to 95°F)

Transit/Storage
Temperature

-15°C to 60°C (5°F to 140°F)

Relative Humidity

0–95% noncondensing

Operating Altitude

Up to 3,048 meters (0–10,000 ft) above sea level

Audible Noise

Less than 55 dBA on line/bypass mode (less than 75% load), room temperature

Fan Speed

Off: when the UPS is in Standby mode or there is no load

Low speed: when the load is < 80%

High speed: when the load is >80% or the UPS is in Battery mode

Surge Suppression

ANSI/IEEE C62.41; 2002 Category B

Safety Conformance

UL 1778 4th Edition;

CSA C22.2, No. 107.3

UL 1778 4th Edition;

CSA C22.2, No. 107.3;

IEC/EN 62040-1-1;

IEC/EN 60950-1

Agency Markings

UL, cUL, NOM/NYCE

UL, cUL

UL, cUL, CE, GS, GOST,

BSMI, S-MARK, KC,
CQC, NRCS, SIRIM

EMC (Class A)

FCC, ICES-003

FCC, ICES-003, VCCI

CE, BSMI, CQC, C-tick