8

lead

motor

8 Leads Series Connected

Eight lead motors can also be connected in two ways: series and parallel. As
with six lead motors, series operation gives you more torque at low speeds and less
torque at high speeds. In series operation, the motor should be operated at 30%
less than the rated current to prevent over heating. The wiring diagrams for eight
lead motors are shown below.

A+

A–

NC

B+

B–

NC

6

lead

motor

Red

Black

Red/

Wht

Green

Grn/Wht

White

A+

A–

NC

B+

B–

NC

6

lead

motor

Grn/Wht

White

Green

Red

Red/

Wht

Black

6 Leads Series Connected

6 Leads Center Tap Connected

8 Leads Parallel Connected

A+

A–

B+

B–

8

lead

motor

-12-

-5-

Orange

Org/Wht

Blk/Wht

Black

Red

Red/

Wht

Yel/
Wht

Yellow

Orange

Org/

Wht

Blk/Wht

Black

Red

Red/Wht

Yel/
Wht

Yel
low

Step

A+

A-

B+

B-

0

+

+

1

+

+

2

+

+

3

+

+

4

+

+

DIR=1

cw

DIR=0

ccw

Step 3 is the Power Up State

Step Table

(full stepping)

Choosing a Power Supply

Voltage

Chopper drives work by switching the voltage to the motor terminals on and off
while monitoring current to achieve a precise level of phase current. To do this
efficiently and silently,

you’ll want to have a power supply with a voltage

rating at least five times that of the motor. Depending on how fast you
want to run the motor, you may need even more voltage than that. More is better,
the only upper limit being the maximum voltage rating of the drive itself: 35 volts.
If you choose an unregulated power supply, do not exceed 24 volts. This is
because unregulated supplies are rated at full load current. At lesser loads, like
when the motor's not moving, the actual voltage can be up to 1.4 times the rated
voltage.

Current
The maximum supply current you could need is the sum of the two
phase currents. However, you will generally need a lot less than that
,
depending on the motor type, voltage speed and load conditions. That's because
the 3535 and 3535 O use switching amplifiers, converting a high voltage and low
current into lower voltage and higher current. The more the power supply voltage
exceeds the motor voltage, the less current you'll need from the power supply. We
recommend the following selection procedure:

1. If you plan to use only a few drives, get a power supply with at least twice the
rated phase current of the motor.
2. If you are designing for mass production and must minimize cost, get one power
supply with more than twice the rated current of the motor. Install the motor in the
application and monitor the current coming out of the power supply and into the
drive at various motor loads. This will tell you how much current you really need so
you can design in a lower cost power supply.

If you plan to use a regulated power supply you may encounter a problem with
current foldback. When you first power up your drive, the full current of both motor
phases will be drawn for a few milliseconds while the stator field is being
established. After that the amplifiers start chopping and much less current is drawn
from the power supply. If your power supply thinks this initial surge is a short
circuit it may "foldback" to a lower voltage. With many foldback schemes the
voltage returns to normal only after the first motor step and is fine thereafter. In that
sense, unregulated power supplies are better. They are also less expensive.