6.6.- Setting power demand utility screens.
Push the key "
" and the following screens will appear by display:
1.- PARAMETER TO CONTROL ("Pd Code xx")
None
00
Three phase active power
kW III
16
Three phase apparent power
kVA III
34
Average three-phase current
AIII
36
Single line current
A1 – A2 – A3 A-PH
Value of power integrated during the programmed demand period.
2.- DEMAND PERIOD ( 1 to 60 min.) ("Pd Per xx")
3.- CLEAR MAXIMUM VALUE IN MEMORY
("CLr Pd xx") no or YES
Programming mode:
- "max" key: allows choosing the different available options.
- "min" key: allows the validation of the blinking digit and go forward to the
next digit (only for the "Pd Per xx" option).
- To pass to the next option press "
".
If you don't want to modify anything, just press the "
" key three times
without modifying any value.