6.4 Register Map
The register map of the DHB-224 meter is presented below.
Notice:
All given addresses are physical addresses. In some computer pro-
grams logical addressing is applied, then addresses must be increa-
sed of 1.
Table 8
Range of addreses
Value type
Description
4000-4049
integer (16 bits)
Value placed in a 16-bit register.
7000-7025
float (32 bits)
Value placed in two successive 16-
bit registers. Registers include the
same data as 32-bit register from
the area 7500. Registers are only for
readout.
7200-7363
float (32 bits)
Value placed in two successive 16-
bit registers. Registers include the
same data as 32-bit register from
the area 7600. Registers can be
read out and written.
7500-7512
float (32 bits)
Value placed in a 32-bit register.
Registers are only for readout.
7600-7663
float (32 bits)
Value placed in a 32-bit register.
Registers can be read out and
written.