• Your fireplace is designed to be used in zero

clearance installations. Wall or framing material

can be placed directly against any exterior sur-

face on the back, sides or top of your fireplace,

except where standoff spacers are integrally

attached. If standoff spacers are attached to your

fireplace, these spacers can be placed directly

against wall or framing material. See framing

details on page 7.

• If you plan on installing a television or enter-

tainment center recessed above your fireplace, it

is recommended that you maintain a minimum

18" above top of louver opening.

• When locating termination cap, it is important

to observe the minimum clearances shown in

Figure 7, page 8.

• If recessing into a wall, you can avoid extra

framing by positioning your fireplace against

an already existing framing member.

• Do not recess termination cap into a wall or

siding.

• You may paint the termination cap with 450º F

(232º C) heat-resistant paint to coordinate with

the exterior finish.

• There must not be any obstruction such as

bushes, garden sheds, fences, decks or util-

ity buildings within 24" from the front of the

termination cap.

• Do not locate termination cap where excessive

snow or ice build up may occur. Be sure to

clear vent termination area after snow falls to

prevent accidental blockage of venting system.

When using snow blowers, do not direct snow

towards vent termination area.

PRE-INSTALLATION

PREPARATION

Continued

CLEARANCES

Minimum clearances to combustibles for the fire-

place are as follows:

*Back and sides

0"

Perpendicular walls

6"

Floor

0"

Ceiling to louver opening

42"

Front

36"

Top of Standoffs

0"

Vent

(See venting instructions

for specific venting

clearances.)

Combustible material with a maximum thick-

ness of 5/8" may be flush with the top front of

fireplace.

* For back and sides of fireplace, do not pack

with insulation or other materials. Zero inch

clearance to combustible materials are for fram-

ing purpose only.

NOTICE: This fireplace is in-

tended for use as supplemental

heat. Use this fireplace along

with your primary heating sys-

tem. Do not install this fireplace

as your primary heat source.

If you have a central heating

system, you may run system’s

circulating blower while using

fireplace. This will help circulate

the heat throughout the house.

In the event of a power outage,

you can use this fireplace as a

heat source.

FRAMING AND FINISHING

Figure 4, page 7, shows typical framing of this

fireplace. Figure 5, page 7, shows framing for

corner installation. All minimum clearances must

be met.

For available accessories for this fireplace, see

Accessories on page 35. If you are using a separate

combustible mantel piece, refer to Figure 6, page

7, for proper installation height. You can install

noncombustible mantels at any height above the

fireplace.
Note:

Noncombustible mantels may discolor!