Venting installation instructions – Desa (V)TC36NE SERIES User Manual

Page 9

Advertising
background image

www.desatech.com

116234-01F

9

VENTING INSTALLATION

INSTRUCTIONS

NOTICE: Read these instruc-

tions completely before at-

tempting installation.

These models are tested and approved for use

with DESA (direct-vent) pipe components and

terminations.

The venting system must terminate on the outside of

the structure and can not be attached to a chimney

or flue system serving a separate solid fuel or gas

burning appliance. A direct-vent appliance must

have its own venting system. DO NOT common

vent this appliance.

These models are approved to be vented either

horizontally through an outside wall or vertically

through a roof or chase enclosure using the fol-

lowing guidelines:

• When venting system terminates horizontally

on an outside wall, you may install a standoff

if the termination cap is to be installed directly

on a combustible finish such as vinyl, wood,

stucco, etc.

• Never run the vent downward as this may

cause excessive temperatures which could

cause a fire.

• Vent pipe air space clearances to combustibles

are 1" on all sides except on the horizontal

sections, which requires 2" clearance from

the top of the pipe. Where the termination cap

penetrates a combustible wall, 1" air space

clearance is required.

• Snorkel terminations are required when

minimum clearance to grade cannot be met (see

Figure 16 on page 13).

• Have fireplace and selected vent components on

hand to help determine the exact measurements

when elbowing or offsetting. Always use wall

firestops when penetrating walls and firestops

when penetrating ceilings or attic spaces.

• If using a venting configuration of only hori-

zontal venting with no vertical run, a 1/4" rise

for every 12" of run toward the termination is

required.

WARNING: Read all instruc-

tions completely and thoroughly

before attempting installation.

Failure to do so could result in

serious injury, property damage

or loss of life.

NOTICE: Failure to follow these in-

structions will void the warranty.

NOTICE: Do not seal termination

cap to vent pipe. Cap must be

removable for vent inspection

and maintenance.

INSTALLATION pRECAUTIONS

• Wear gloves and safety glasses for protection

• Use extreme caution when using ladders or

when on roof tops

• Be aware of electrical wiring locations in walls

and ceilings

The following actions will void the warranty on

your venting system:

• Installation of any damaged venting component

• Unauthorized modification of the venting sys-

tem (Do not cut or alter vent components)

• Installation of any component part not manu-

factured or approved by DESA

• Installation other than as instructed by these

instructions

WARNING: This gas fireplace

and vent assembly must be

vented directly to the outside.

The venting system must NEVER

be attached to a chimney serv-

ing a separate solid fuel burning

appliance. Each direct-vent gas

appliance must use a separate

vent system. Do not use com-

mon vent systems.

WARNING: Vent pipe air

space clearances to combus-

tibles are 1" on all sides except

on the horizontal sections,

which require 2" clearances

from the top of the pipe. Where

the termination cap penetrates

a combustible wall, 1" air space

clearance is required.