Vent Requirements

The gas appliance and vent system must be vented directly to the outside of the building, and
never be attached to a chimney serving a separate solid fuel or gas-burning appliance. Each
direct vent gas appliance must use it's own separate vent system.

Vent Clearances

The vent must maintain the required clearance to combustible materials to prevent a fire. Do
not fill air spaces with insulation.

Sides

1"

Above

3"

Below Horizontal or 45° Section

1"

Use a firestop when

passing through any

wall (WARNING: some

firestops provide a 1"

clearance above the

vent -- 3" is required for

this heater).

Min. 3" Clearance

Above the Vent

Min. 1" Clearance to

the side of vent

1" Clearance to the sides

after the first firestop.

Use a firestop whenever

passing through a

ceiling, enclosure or

floor penetration.

Altitude Considerations

This heater has been tested at altitudes ranging from sea level to 8,000 feet (2,400 M). In this testing we
have found that the heater, with its standard orifice, burns correctly with just an air shutter adjustment.

Failure to adjust the air shutter properly may lead to improper combustion which can create a safety hazard.
Consult your dealer or installer if you suspect an improperly adjusted air shutter.

Approved Vent

Use 8" diameter Model GS Direct Vent manufactured by Simpson Dura-Vent only. Follow the
installation instructions included with the vent. For the nearest Simpson Dura-Vent supplier,
call (800) 835-4429.

Always use the high-wind termination (if applicable).