Installation (for qualified installers only)

© Travis Industries

4060517

100-01158

Horizontal Termination - NG (Natural Gas)

•

0 or 2 90° Elbows may be used. See "Horizontal Termination with 45° Elbow" if installing into
a corner application.

•

If using a Snorkel Termination (14” or 36”) add the snorkel height to the vertical height (snorkel
terminations are used primarily for basement installations).

•

The termination must fall within the shaded area shown in the chart. Use the indicated
restrictor position.

5 feet

10 feet

0 feet

0 feet

5 feet

5 feet

0 feet

0 feet

10 feet

5 feet

10 feet

14'

(max)

10 feet

Restrictor

Position # 1

Diffuser

Removed

14 feet

(max)

NOTE:

Horizontal sections require a 1/4" rise every

12" of travel.

NOTE:

Restrictor positions are based upon lab tests.

14 feet

(max)

14 feet
(max)

Restrictor Position # 1

Diffuser Installed