Installation – Desa F48H(i)(R) User Manual

Page 5

Advertising
background image

www.desatech.com

122272-01C

5

HEARTH ExTENSION

A hearth extension projecting a minimum of
20" in front of and a minimum of 12" beyond
each side of the fireplace opening is required
to protect combustible floor construction
in front of the fireplace. Fabricate a hearth
extension using a material which meets the
following specifications: a layer of noncom-
bustible, inorganic material having a thermal
conductivity of K=0.84 BTU IN/FT, HR. F (or
less) at 1" thick. For example, if the material
selected has a K factor of 0.25, such as glass
fiber, the following formula would apply:

0.25 x 1.0" = 0.30" thickness required

0.84

Thermal conductivity "K" of materials can be
obtained from the manufacturer or supplier of
the noncombustible material. If the hearth ex-
tension is to be covered, use noncombustible
material such as tile, slate, brick, concrete,
metal, glass, marble, stone, etc. Provide a
means to prevent the hearth extension from
shifting and seal gap between the fireplace
frame and hearth extension with a noncom-
bustible material (see Figure 3).

WARNING: Hearth extension

is to be installed only as shown

in Figure 3.

installation

Continued

Figure 3 - Hearth Extension

Seal Gap

Fireplace Front

Ember Protector

Fireplace Front
Raised Hearth

Fireplace Front
Elevated

Ember Protector

Ember Protector

Seal Gap

Hearth

Extension

MANTELS

A mantel may be installed if desired (see
Figure 4). Woodwork such as wood trims,
mantels or any other combustible material
projecting from the front face must not be
placed within 12" of the fireplace opening.
Combustible materials above 12" and pro-
jecting more than 1

1

/

2

" from the fireplace

must not be placed less than 15" from the
top opening of the fireplace (NFPA STD 211,
Sec. 7-3.3.3).
Mantels or any other combustible material
also may come up to the side edge of the
black metal face of the fireplace just as long
as the projection from the front face fall within
the limit shown in Figure 4.

12

1

/

4

" Ref.

15" Min.

12" Min.

1

1

/

2

" Max.

3" Nom.

33°

Combustible
Material

Safe
Zone for
Projection of
Combustible
Materials

Fireplace Opening

Upper

Section of

Fireplace

Figure 4 - Mantel Clearances to

Combustible Material

6"

Ref.

OPTIONAL OUTSIDE AIR KIT
(MoDeL Ak4/Ak4f)

Installation of an outside air kit should be per-
formed during rough framing of fireplace due
to nature of it's location. Outside combustion
air is accessed through a vented crawl space
(AK4F) or through a sidewall (AK4). This fire-
place is equipped with a barometric damper
which allow outside air to flow into fireplace
automatically when needed.