installation

Continued

Figure 9 - Elbow Offset

B

A

Screws

FIRESTOP SPACERS (FS-10)

Firestop spacers are required at each point
where chimney penetrates a floor space.
Their purpose is to establish and maintain
required clearance between chimney and
combustible materials. When pipe passes
through a framed opening into a living space
above, firestop must be placed onto ceiling
from below as shown in Figure 10.
They also provide complete separation from
one floor space to another or attic space as
required by most codes. When the double wall
pipe passes through a framed opening into an
attic space, the firestop must be placed into
an attic floor as shown in Figure 11.

Figure 10 - Firestop Spacer with Living

Space Above Ceiling

Figure 11 - Firestop Spacer with Attic

Space Above Ceiling

Existing
Ceiling
Frame

Firestop
Spacer

Screws or
Staples
(Min. of 8)

Firestop
Spacer

Screws or Staples
(Min. of 8)

PENETRATING ROOF

To maintain a 2" clearance to pipe on roof with
a pitch, a rectangular opening must be cut.
1. Determine center point through which pipe

will penetrate roof.

2. Determine center point of roof. Pitch is

the distance the roof drops over a given
span, usually 12".

3. Use roof opening chart (Figure 12) to

determine correct opening length and
flashing required.

4. Remove shingles around opening mea-

sured. Cut out this section.

5. Add next sections of pipe until end

penetrates roof line. Check to see that
proper clearances are maintained. Extend
chimney by adding sections of double wall
pipe until pipe is minimum of 30" above
highest point of roof cutout. Termination
and chimney must extend a minimum of
36" above highest point where it passes
through roof.

Pitch

Slope

Opening

"A" Max.

Used Flashing

Model No.

Flat

19.5"

V6F-10DM

0-6/12

26.6°

22'

V6F-10DM

6/12-12/12 45.0°

27"

V12F-10DM

Existing
Ceiling
Frame

19.5" Min.

30" Min.

2" Min.

2" Min.

2" Min.

Opening "A"

Figure 12 - Roof Opening Measurements