FireBox inSTALLATion

Continued

VenTing inSTALLATion

OPTIONAL OUTSIDE AIR KIT

The installation of an outside air kit should be per-

formed during the rough framing of the firebox due

to the nature of it’s location. Outside combustion air

is accessed through and exterior wall or a vented

crawl space (see Figure 12, page 7).

CAUTION: Air inlet ducts

must not terminate in attic

space.

The maximum height for the

air vent can not exceed 3 feet

below the flue gas outlet of the

termination.

Avoid installing outside air eyebrow in areas

where inlet opening may be blocked by snow,

bushes or other obstacles. It should also be

located beyond the reach of small children.
For further details on installation of outside air

kit, please refer to instructions included with

air kit. For operating instructions, please refer

to your owner's manual.

8" Max.

“K” Factor

.84

1

1

/

2

" Typ.

1

1

/

2

" Typ.

Noncombustible

Hearth

Extension

“Z” Type Ember

Protector

Noncombustible

Hearth Extension

Ember Protector

Figure 11 - Raised Hearth Extension

Figure 9 - Nailing Flanges

Nailing

Flanges

Prepared

Framing

Nails or

Screws

1/2" (1.27 cm)

Minimum to

Combustibles

HEARTH ExTENSION

A hearth extension projecting a minimum of

16" in front of and a minimum of 8" beyond

each side of the firebox opening is required to

protect combustible floor construction in front

of firebox (see Figure 10). Fabricate a hearth

extension using a material which meets the

following specifications: a layer of noncom-

bustible, inorganic material having a thermal

conductivity of K=0.84 BTU IN/FT, HR. F (or

less) at 1" thick. For example, if the material

selected has a K factor of 0.25, such as glass

fiber, the following formula would apply:

0.25 x 1.0" = 0.30" thickness required

0.84

NONCOMBUSTIBLE

HEARTH EXTENSION

52

1

/

2

" MIN.

(133.3cm)

36

1

/

2

" MIN.

(92.7cm)

8" MIN.

(20.3cm)

16" MIN.

(40.6cm)

Figure 10 - Hearth Extension

Thermal conductivity "K" of materials can be

obtained from manufacturer or supplier of

noncombustible material.
If hearth extension is to be raised, a “Z” type

ember protector must be used (see Figure 7,

page 5, and Figure 11)