BECKHOFF BK2000 User Manual

Page 11

Advertising
background image

Basic information

BK2000

11













Insulation test












PE power contacts

The connection between bus couplers and bus terminals is automatically
effected by latching the components together. The K-bus is responsible for
passing data and power to the electronic components of the bus terminals.
In the case of digital bus terminals, the field logic receives power via the
power contacts. Latching the components together has the effect that the
series of power contacts constitutes a continuous power track. Please refer
to the circuit diagrams of the bus terminals: some bus terminals do not loop
these power contacts through, or not completely (e.g. analog bus terminals
or 4-channel digital bus terminals). Each power input terminal interrupts the
series of power contacts and constitutes the beginning of a new track. The
bus coupler can also be used to supply power to the power contacts.

The power contact labeled “PE” can be used as protective earth or ground.
This contact stands proud for safety reasons and can carry short-circuit
currents of up to 125A. Note that in the interests of electromagnetic
compatibility the PE contacts are capacitively connected to the supporting
track. This may lead to spurious results and even damage to the terminal
when you test the insulation (e.g. insulation test for breakdown using a
230V mains supply to the PE line). You should therefore disconnect the PE
line on the bus coupler while you carry out insulation tests. You can
disconnect other power supply points for the duration of the test by drawing
the power supply terminals out from the remaining row of terminals by at
least 10mm. If you do this, there will be no need to disconnect the PE
connections.

The protective earth power contact (“PE”) may not be used for any other
connections.

Electrical data

Lightbus couplers may have different configuration levels. The electrical
data specific to the fieldbus is listed in the appropriate chapter. The
following data distinguishes between the standard version and the
economy version (BK2000 and BK2010). Either version is fully compatible
to the Beckhoff-Lightbus, but the economy version has only a limited
number of I/O points, which is why it permits you to attach only digital
inputs and outputs.

Technical data

Beckhoff-Lightbus coupler BK2000

Economy coupler BK2010

Voltage supply

24 V, + / - 10%

Input current

105 mA typical

85 mA typical

900 mA max.

300 mA max.

Output current K-bus

1.75 A max.

0.5 A max.

Supply isolation

500 Veff (K-bus / supply voltage)

Number of bus terminals

64

Digital peripheral signals

256 inputs and outputs

256 inputs and 256 outputs

Analog peripheral signals

128 inputs and outputs

--

Peripheral bytes

512 input and 512 output bytes

32 input and 32 output bytes

Configuration interface

Available for KS2000

Baud rates

2,5 MBaud

Voltage power contact

24V DC / AC

Current load power con.

10 A

Max. voltage capacity

500 Veff (power contact / supply voltage)

Weight approx.

150g

130g

Operating temperature

0°C ... +55°C

Storage temperature

-25°C ... +85°C

Relative humidity

95% non-condensing

Vibration /shock resistance

according to IEC 68-2-6 / IEC 68-2-27

Interference resistance.
Burst / ESD

according to EN 61000-4-4/ EN 61000- 4-, limit EN 50082-2-4

Orientation for mounting

any

Type of fuse

IP20