BK2000 diagnostic LEDs

Attention must be paid to the fact that there is a connection between the
green I/O LED and the field bus. The I/O LED lights up in connection with
access to the internal K-bus. The green I/O LED does not light up until a
trigger begins via the field bus. This means that the field bus must access
the bus coupler and the controller software must clear a cyclical trigger.
The green I/O LED indicates access to the internal K-bus and is reset after
100 ms.

The bus coupler queries the configuration of the bus terminals after
switching on and does not exchange data with the terminals. That is to say,
the red I/O LED goes off after an error-free startup without the green I/O
LED having to light up. The green I/O LED does not light up until data
exchange is begun via the Beckhoff-Lightbus.

CYC

ERR

WD

Meaning

Remedy

lit

off

lit

Cyclic telegrams are passing via the ring.
Inputs are read and outputs are set.

off

flashing

off

Occasional CRC error (green I/O LED lit)
Inputs are read; outputs are not updated.

Fiber-optic connection damaged

off

lit

off

Bus error (physical). Errored telegrams
are passing through the ring, e.g. fiber-
optic line damaged or previous module
malfunctioning, connector not inserted
correctly.

Check:
whether the fiber-optic cable is inserted
whether the fiber-optic cable has a
discontinuity
whether previous units are operable.

off

off

off

No operating voltage, severe error; no
functioning

flashing

off

off

The controller is only occasionally
accessing the bus. The outputs drop out.

Revise the controller software

lit

off

off

The ring is functioning, but the bus
coupler is not addressed.

Revise the controller software or
allocation list

lit

off

lit

I/O RUN is not lit, the bus terminal is
addressed, but the data exchange via the
K-bus has not been started.

Add the trigger call to the controller
software