Electrical data – BECKHOFF BK4000 User Manual

Page 12

Advertising
background image

Basic information

12

BK4000


Electrical data

The InterBus couplers differ by virtue of their capacity levels. The electrical
data specific to the field bus is listed in this chapter. The following data
differs depending on whether a standard or an economy variant is meant
(BK4000, BK4500 and BK4010). Contrary to the standard variant, the eco-
nomy variant limits the number of I/O points. Thus, there is no possibility of
connecting inputs and outputs other than digital inputs and outputs.

Technical data

InterBus-coupler BK4000/BK4500

Economy -coupler BK4010

Power supply

24 V, - 15% + 20%

Input current

105 mA typ. ( 30 digital inputs- / 20 outputs )

85 mA typ.

900 mA max.

300 mA max.

K-Bus output current

1750 mA max.

500 mA max.

Potential isolation

500 Vrms (K-bus / power supply to periphery)

Number of bus terminals

64 including potential feed terminals and end terminal

Digital peripheral signals

256 inputs and outputs

256 inputs and outputs

Analog peripheral signals

32 inputs and outputs#1

--

Peripheral bytes

64 input bytes and 64 output bytes

32 input and 32 output bytes

Configuration interface

available for KS2000

Baud rates

500 KBaud in conformity with the standard

Power contact voltage

24V DC / AC

Power contact current load

10 A

Dielectric strength

500 Vrms (Power contact / InterBus signal voltage), incoming interface

Typical weight

170g

Operating temperature

0°C ... +55°C

Storage temperature

-20°C ... +85°C

Relative humidity

95%, no condensation

Vibration / shock strength

in conformity with IEC 68-2-6 / IEC 68-2-27

EMC strength,. Burst / ESD

in conformity with EN 61000-4-4/ EN 61000-4, limit EN 50082-2-4

Installation position

any

Type of protection

IP20



Current consumption on the
K-Bus

For operation of the K-Bus electronics, the bus terminals require power
from the K-Bus which the bus coupler supplies. Refer to the catalog or the
corresponding data sheets of the bus terminals for details of the current
consumption of the K-Bus. At the same time, pay attention to the maximum
output current of the bus coupler that is available for powering the bus ter-
minals. By means of a special power supply terminal, an infeed into the K-
Bus is possible at any point. Please consult Beckhhoff’s technical support
for details of how to use a power supply terminal.