Electrical data – BECKHOFF BK7500 User Manual

Page 13

Advertising
background image

Basic information

BK7500

13


Electrical data

The SERCOS coupler BK7500 and BK7510 differ by virtue of their capacity
levels. The following data distinguishes between a standard and an
economy variant (BK7500 and BK7510). Compatability with the other
SERCOS components is guaranteed in any case. Contrary to the standard
bus coupler, the economy variant is limited of the number of I/O´s. Thus,
there is no possibility of connecting inputs and outputs other than digital
ones. The following table lists an overview of all data:

Technical data

Beckhoff SERCOSCoupler BK7500

Supply voltage

24 V, - 15% +20%

Input current

105 mA typ.

900 mA max.

K bus supply current up to

1.75 A max.

Potential isolation

500 Vrms (K-bus / peripheral voltage)

Number of bus terminals

64

Digital peripheral signals

256 inputs and outputs

Analog peripheral signals

128 inputs and outputs

Peripheral bytes

512 input byte and 512 output byte

Configuration

Via SERCOS Master or KS2000

Fieldbus medium

Fibre optic Z1100

Plug connection

F-SMA-Norm IEC 872-2 Z1003 for Z1100

Baud rate

2 or 4 Mbaud ( 8 and 16 Mbaud in preparation)

Voltage of the power contact 24V DC / AC
Power contacts current
drawn

10 A

Electric strength

500 Vrms (power contact / supply voltage)

Typical weight

150g

Operating temperature

0°C ... +55°C

Storage temperature

-25°C ... +85°C

Relative humidity

95% without dew formation

Vibration/shock stability

According to IEC 68-2-6 / IEC 68-2-27

EMC-immunity. Burst / ESD

According to EN 61000-4-4 / EN 61000-4-2 limit value according to EN 50082-2-4

Installation location

Arbitrary

Protection class

IP20


Current consumption on the
K-Bus

For operation of the K-bus electronics, the bus terminals require energy
from the K-bus that is supplied by the bus coupler. Refer to the catalog or
the corresponding data sheets of the bus terminals for details of the K-bus
current consumption. In doing so, pay attention to the maximum output
current of the bus coupler that is available for powering the bus terminals.
Using a special power supply terminal (KL9400), power can be fed back
into the K-bus at any chosen point. If you wish to use a power supply
terminal, please contact Beckhoff’s technical support. .