24

BK7500

IDN

Name

Type

Attributes

Default
value

Function

S-2-0001

Channel type

Variable

Read/Write

I/O data channel + 0001

Meaning

The channel type describes the type of the terminal. This also depends on
the IDN P-0-0001 (see Table xxx).

KL1xxx (strict)

0x0001 16 bit data (without KL1501)

KL1xxx (compact)

0x0001 32 bit data (without KL1501)

KL2xxx (strict)

0x0001 16 bit data (without
KL2502)

KL2xxx (compact)

0x0001 32 bit data (without
KL2502)

KL1501 (strict/ compact)

0x8006 16 bit data

KL2502 (strict)

0x8003 16 bit data

KL3xxx (strict)

0x8002 16 bit data

KL3xxx (compact)

0x8002 32 bit data

KL4xxx (strict)

0x0003 16 bit data

KL4xxx / KL2502 (compact)

0x8003 16 bit data

KL5xxx (strict / compact)

0x8007 16 bit data

KL6xxx (standard)

0x8004 16 bit data

KL6xxx (alternative)

0x8004 16 bit data

IDN

Name

Type

Attrib
utes

Default
value

Function

S-2-0002

Channel IDN list

IDN

I/O data channel + 0002

Meaning

This list contains the identification numbers supported by the relevant
channel.

IDN

Name

Type

Attrib
utes

Default
value

Function

S-2-0003

Occupied inputs

Uint 16

Read

I/O data channel + 0003

Meaning

This operating data contains a bit mask specifying the occupied inputs for
this channel. Every bit that is set represents a usable input.

IDN

Name

Type

Attrib
utes

Default
value

Function

S-0-0011 I/O state class 1

Uint 16

Read

Meaning

Affects bits 11-13 in the I/O station's status word.


IDN

Name

Type

Attrib
utes

Default
value

Function

S-0-0030 Manufacturer version

Variable, 1 byte

Read

0xXXXX

Meaning

Shows the manufacturer version in the operating data.