BECKHOFF BK8000 User Manual

Page 20

Advertising
background image

RS 485 Coupler BK8000

20

BK8000


The following table provides a list of the plugged-in terminals in their
physical arrangement on the coupler with the affiliated mapped bits in the
bus coupler's process image.

Position

Function module on the rail

POS00

BK8000

POS01

KL1002 (2 I)

POS02

KL1002 (2 I)

POS03

KL1002 (2 I)

POS04

KL1114 (4 I)

POS05

Kl1114 (4 I)

POS06

KL3002 (2 x 16 I)

POS07

KL9200 (-)

POS08

KL2012 (2 O)

POS09

KL2012 (2 O)

POS10

KL2012 (2 O)

POS11

KL2012 (2 O)

POS12

KL4002 (2 x 16 O)

POS13

KL9010 (-)


Therefore, the process image on the bus coupler has the following
breakdown:

Process image of the inputs:

Relative byte address
in the bus coupler's PII

Bit position

Position in the
block

Bus terminal

0, 1

None

POS06

KL3002, Channel 1

2, 3

None

POS06

KL3002, Channel 2

4

0

POS01

KL1002, Channel 1

4

1

POS01

KL1002, Channel 2

4

2

POS02

KL1002, Channel 1

4

3

POS02

KL1002, Channel 2

4

4

POS03

KL1002, Channel 1

4

5

POS03

KL1002, Channel 2

4

6

POS04

KL1114, Channel 1

4

7

POS04

KL1114, Channel 2

5

0

POS04

KL1114, Channel 3

5

1

POS04

KL1114, Channel 4

5

2

POS05

KL1114, Channel 1

5

3

POS05

KL1114, Channel 2

5

4

POS05

KL1114, Channel 3

5

5

POS05

KL1114, Channel 4


Process image of the outputs:

Relative byte address in
the bus coupler's PIO

Bit position

Position in the
block

Bus terminal

0, 1

None

POS12

KL4002, Channel 1

2, 3

None

POS12

KL4002, Channel 2

4

0

POS08

KL2012, Channel 1

4

1

POS08

KL2012, Channel 2

4

2

POS09

KL2012, Channel 1

4

3

POS09

KL2012, Channel 2

4

4

POS10

KL2012, Channel 1

4

5

POS10

KL2012, Channel 2

4

6

POS11

KL2012, Channel 1

4

7

POS11

KL2012, Channel 2

Advertising