BECKHOFF KL5111-0000 User Manual

Page 16

Advertising
background image

Register description

14

KL5111-0000

Bit

Name

Function

SB.7

RegAcc=0

Acknowledge for process data exchange

SB.6 -

reserved

SB.5 -

reserved

SB.4

Overflow

This bit is set if an overflow (65535 to 0) of the 16-bit counter occurs.
It is reset if the counter exceeds a third of the measurement range
(21845 to 21846) or as soon as an underflow occurs.

SB.3

Underflow

This bit is set if an underflow (0 to 65535) of the 16-bit counter
occurs. It is reset when the counter drops below two thirdds of the
measurement range (43690 to 43689) or as soon as an overflow
occurs.

SB.2

CntSet_Acc

The data for setting the counter has been accepted from the terminal.

SB.1

RD_Period_Q

if bit R32.8 of Feature Register is not set:
Die data bytes DataIN2, DataIN3 and DataIN4 contain the period

if bit R32.8 8 of Feature Register is set:
DataIN3 und DataIN4 contain the counted pulses

SB.0

Latch_Val

A zero point latch has occurred. The data DIN3, DIN4 in the process
image corresponds to the latched value when the bit is set if the
period has not been requested. To reactivate the latch input,
EN_LATC must first be cancelled, acknowledgement of cancellation
must be waited for and then the bit must be set again. (Not used if
the V/R mode is active, i.e. bit 15 is set in the feature register).

or if bit 0 is set in the feature register:

Bit

CB.7 CB.6

CB.5 CB.4 CB.3 CB.2

CB.1

CB.0

Name

RegAcc -

A-Signal B-Signal C-Signal CntSet_Acc RD_Period_Q Latch_Val

Bit

Name

Function

SB.7

RegAcc=0

Acknowledge for process data exchange

SB.6 -

reserved

SB.5

A-Signal

status of the input A

SB.4

B-Signal

status of the input B

SB.3

C-Signal

status of the input C

SB.2

CntSet_Acc

The data for setting the counter has been accepted from the terminal.

SB.1

RD_Period_Q

if bit R32.8 of Feature Register is not set:
Die data bytes DataIN2, DataIN3 and DataIN4 contain the period

if bit R32.8 8 of Feature Register is set:
DataIN3 und DataIN4 contain the counted pulses

SB.0

Latch_Val

A zero point latch has occurred. The data DataIN3, DataIN4 in the
process image corresponds to the latched value when the bit is set if
the period has not been requested. To reactivate the latch input,
EN_LATC must first be cancelled, acknowledgement of cancellation
must be waited for and then the bit must be set again. (Not used if
the V/R mode is active, i.e. bit 15 is set in the feature register).

Advertising