4 safety parameters, 5 characteristic curve of the inputs – BECKHOFF EL1904 User Manual

Page 17

Advertising
background image

Product description

EL1904

15

Product designation

EL1904

Permissible installation position

see section The TwinSAFE terminals must be
installed in a control cabinet or terminal box with
IP54 protection class according to IEC 60529 as a
minimum.

Approvals

CE, cULus, ATEX, TÜV SÜD

3.4 Safety parameters

Key figures

EL1904

Lifetime [a]

20

Prooftest Interval [a]

not required

1)

PFH 1.11E-09
%SIL3 1.11%
PFD 8.29E-05
%SIL3 8.29%
MTTFd [a]

>100

DC >99%
Performance level

PL e

Category 4
HFT 1
Element classification

2)

Type

A

1)

Special proof tests are not required during the entire service life of the EL1904 EtherCAT terminal.

2

) Classification according to IEC 61508-2:2010 (chapters 7.4.4.1.2 and 7.4.4.1.3)

The EL1904 EtherCAT Terminal can be used for safety-related applications within the meaning of
IEC 61508:2010 up to SIL3 and EN ISO 13849-1 up to PL e (Cat4).

3.5 Characteristic curve of the inputs

The characteristic curve of the inputs is similar to type 3 according to EN 61131-2.