4 diagnostics – BECKHOFF EL1904 User Manual

Page 37

Advertising
background image

Operation

EL1904

35

4.4 Diagnostics

4.4.1 Diagnostic

LEDs

The LEDs Diag 1 to Diag 4 display diagnostic information for the EL1904.

4.4.1.1

Diag 1 (green)

The Diag 1 LED indicates the state of the TwinSAFE interface.

Flashing Code

Meaning

LED illuminated continuously normal

operation:

TwinSAFE communication OK

rapid flickering, alternating with 1 flash pulse

Error in S parameter (TwinSAFE parameter)

rapid flickering, alternating with 2 flash pulses

Error in I parameter (Individual parameter)

rapid flickering, alternating with 3 flash pulses

Waiting for S and I parameter

rapid flickering, alternating with 4 flash pulses

S- and I-parameter correct:
waiting for first host message

rapid flickering, alternating with 5 flash pulses

Watchdog error

rapid flickering, alternating with 6 flash pulses

CRC error

rapid flickering, alternating with 7 flash pulses

Sequence number error

rapid flickering, alternating with 8 flash pulses

Communication error in the TwinSAFE protocol

4.4.1.2

Diag 2 (red)

The Diag 2 LED illuminates red if the terminal detects an external supply or cross-circuit. The LED
extinguishes once the error is rectified.

Advertising