BECKHOFF EL1904 User Manual

Page 35

Advertising
background image

Operation

EL1904

33

Parameter overview

PrmName

Meaning

Values

FSoE_Address

DIP switch address

1 to 65535

Operating Mode

Digital / standstill monitoring 1 and 2

Digital / standstill 1 and 2

Sensor test channel
1 active

The clock signal for connection Input1+ is
checked at connection Input1-.

true / false

Sensor test channel
2 active

The clock signal for connection Input2+ is
checked at connection Input2-.

true / false

Sensor test channel
3 active

The clock signal for connection Input3+ is
checked at connection Input3-.

true / false

Sensor test channel
4 active

The clock signal for connection Input4+ is
checked at connection Input4-.

true / false

Logic channel 1
and 2

Logic of channels 1 and 2

- single logic
- asynchronous repetition OSSD
(sensor test must be switched off)
- any pulse repetition OSSD
(sensor test must be switched off)
- short cut is no module fault

Logic channel 3
and 4

Logic of channels 3 and 4

- single logic
- asynchronous repetition OSSD
(sensor test must be switched off)
- any pulse repetition OSSD
(sensor test must be switched off)
- short cut is no module fault

Store Code

This parameter is required for the
TwinSAFE Restore Mode

0x0000

Project CRC

This parameter is required for the
TwinSAFE Restore Mode

0x0000