5 maintenance – BECKHOFF EL1904 User Manual

Page 40

Advertising
background image

Operation

38

EL1904

4.5 Maintenance

The TwinSAFE terminals are maintenance-free!

WARNING

Observe the specified environmental conditions!

Please ensure that the TwinSAFE terminals are only stored and operated under the
specified conditions (see technical data).


If the terminal is operated outside the permitted temperature range it will switch to Global Fault state.

4.5.1 Cleaning

Protect the TwinSAFE terminal from unacceptable soling during operation and storage!

If the TwinSAFE terminals were subjected to unacceptable soiling they may no longer be operated!

WARNING

Have soiled terminals checked!

Cleaning of the TwinSAFE terminal by the user is not permitted!
Please send soiled terminals to the manufacturer for inspection and cleaning!

4.5.2 Service

life

The TwinSAFE terminals are designed for a service life of 20 years.

Due to the high diagnostic coverage within the lifecycle no special proof tests are required.

The TwinSAFE terminals bear a date code, which is composed as follows:

Date code: CW YY SW HW

Legend:
CW:

Calendar week of manufacture

YY:

Year of manufacture

SW: Software

version

HW: Hardware

version

Example: Date code

17 11 05 00

Calendar week:

17

Year:

2011

Software version:

05

Hardware version:

00


In addition the TwinSAFE terminals bear a unique serial number.