2 diagnostic objects – BECKHOFF EL1904 User Manual

Page 39

Advertising
background image

Operation

EL1904

37

4.4.2 Diagnostic

objects

CAUTION

Do not change CoE objects!

Do not change any of the CoE objects in the TwinSAFE terminals! Any modifications
(e.g. via the TwinCAT System Manager) in the CoE objects permanently put the
terminals in the fail-stop state or result in unexpected behavior of the terminals!


The CoE objects FA80

hex

indicate the current internal temperature values of the EL1904.

Index FA80

hex

: Internal temperature values

Index

Name

Meaning

Flags

Default

FA80:01

Temperature 1

Temperature measurement 1

RO

0

bin

FA80:02

Temperature 2

Temperature measurement 2

RO

0

bin


The CoE objects 800E

hex

display further diagnostic information.

Index 800E

hex

: Diagnostic objects

Index

Name

Meaning

Flags Default

800E:0

Diag

The following sub-indices contain detailed
diagnostic information.

RO

800E:0A

Sensor test error

Bit

Error during the sensor test

RO

0 1

bin

Error at input 1

0

bin

1 1

bin

Error at input 2

0

bin

2 1

bin

Error at input 3

0

bin

3 1

bin

Error at input 4

0

bin

800E:0B

Error during two-
channel evaluation

Bit

Error during the contiguous evaluation of
two channels, i.e. the two channels
contradict each other.

RO

0 1

bin

Error in the first input pair

0

bin

1 1

bin

Error in the second input pair

0

bin

800E:0C

Error in the safety
mat operating
mode: input pair
disagree

Bits Error in the input pair

RO

1, 0 11

bin

Error in the first input pair

00

bin

3, 2 11

bin

Error in the second input pair

00

bin

800E:0D

Error in the safety
mat operating
mode: external
supply

Bit

Error in the test pulses in the safety mat
operating mode; i.e. the terminal has
detected an external supply.

RO

0 1

bin

Error at input 1

0

bin

1 1

bin

Error at input 2

0

bin

2 1

bin

Error at input 3

0

bin

3 1

bin

Error at input 4

0

bin

Note

Differing diagnostic messages possible

Due to the variable order or execution of the test series, diagnostic messages differing
from those given in the table above are possible.