3 power supply, 1 power connection – BECKHOFF EP9128 User Manual

Page 34

Advertising
background image

Mounting and cabling

ZK1090­9191­

0001

0002

0005

0010

0020

0030

0040

0050

0100

0150

Length

0.17 m

0.26 m

0.5 m

1.0 m

2.0 m

3.0 m

4.0 m

5.0 m

10 m

15 m

ZK1090­9191­

0200

0250

0300

0350

0400

0450

0500

Length

20 m

25 m

30 m

35 m

40 m

45 m

50 m

4.3

Power supply

4.3.1

Power Connection

The feeding and forwarding of supply voltages is done via two M8 connectors at the bottom end of the
modules:

• IN: left M8 connector for feeding the supply voltages

• OUT: right M8 connector for forwarding the supply voltages

Fig. 43: EtherCAT Box, Connectors for power supply

Table 1: PIN assignment

Pin

Voltage

1

Control voltage Us, +24 V

DC

2

Auxiliary voltage Up, +24 V

DC

3

GNDs*

*) may be connected internally to each other depending on the module: see specific
module descriptions

4

GNDp*

The pins M8 connectors carry a maximum current of 4 A.

Two LEDs display the status of the supply voltages.

Attention

Don't confuse the power connectors with the EtherCAT connectors!

Never connect the power cables (M8, 24 V

DC

) with the green marked EtherCAT sockets of

the EtherCAT Box Modules! This can damage the modules!

Control voltage Us: 24 V

DC

Power is supplied to the fieldbus, the processor logic, the inputs and the sensors from the 24 V

DC

 control

voltage Us. The control voltage is electrically isolated from the fieldbus circuitry.

EP9128

34

Version 2.1.0