background image

Mounting and cabling

Further available power cables may be found in the Beckhoff catalog or on our internet pages (http://
www.beckhoff.com).

Technical data

Technical data

Rated voltage according to IEC60 664­1

60 V

AC

 / 75 V

DC

Contamination level according to IEC 60 664­1

3/2

Insulation resistance IEC 60 512­2

>10

9

W

Current carrying capacity according to IEC 60512­3

4 A

Volume resistance according to IEC 60512­2

< 5 mW

Protection class according to IEC 60529

IP65/66/67, when screwed together

Ambient temperature

­30°C to +80°C

4.3.4

Power cable conductor losses

The ZK2020­xxxx­yyyy power cables should not exceed the total length of 15 m at 4 A (with continuation).
When planning the cabling, note that at 24 V nominal voltage, the functionality of the module can no longer
be assured if the voltage drop reaches 6 V. Variations in the output voltage from the power supply unit must
also be taken into account.

Fig. 46: Power cable conductor losses

Example

8 m power cable with 0.34 mm² cross­section has a voltage drop of 3.2 V at 4 A.