Mounting and cabling

Note

EP92x4 Power Distribution Modules

With EP9214 and EP9224 Power Distribution Modules intelligent concepts for voltage sup­
ply are available. Further information may be found under www.beckhoff.com/EP9224.

4.4

UL Requirements

The installation of the EtherCAT Box Modules certified by UL has to meet the following requirements.

Supply voltage

CAUTION

CAUTION!

• by a 24 V

DC

 supply voltage, supplied by an isolating source and protected by means of

a fuse (in accordance with UL248), rated maximum 4 Amp, or

• by a 24 V

DC

 power source, that has to satisfy NEC class 2.

NEC class 2 power supply shall not be connected in series or parallel with another
(class 2) power source!

CAUTION

CAUTION!

To meet the UL requirements, the EtherCAT Box Modules must not be connected to unlim­
ited power sources!

Networks

CAUTION

CAUTION!

To meet the UL requirements, EtherCAT Box Modules must not be connected to telecom­
munication networks!

Ambient temperature range

CAUTION

CAUTION!

To meet the UL requirements, EtherCAT Box Modules has to be operated only at an ambi­
ent temperature range of 0 to 55°C!

Marking for UL

All EtherCAT Box Modules certified by UL (Underwriters Laboratories) are marked with the following label.

Fig. 47: UL label

EP9128

39

Version 2.1.0