Mounting and cabling

Auxiliary voltage Up 24 V

DC

The Auxiliary voltage Up supplies the digital outputs; it can be brought in separately. If the load voltage is
switched off, the fieldbus functions and the power supply and functionality of the inputs are retained.

Redirection of the supply voltages

The IN and OUT power connections are bridged in the module (not IP204x­Bxxx and IE204x). The supply
voltages Us and Up can thus easily be transferred from EtherCAT Box to EtherCAT Box.

Attention

Pay attention to the maximum permissible current!

Pay attention also for the redirection of the supply voltages Us and Up, the maximum per­
missible current for M8 connectors of 4 A must not be exceeded!

Supply via EP92x4­0023 PowerBox modules

If the machine requires higher current or if the EtherCAT Box Modules are installed far away from the control
cabinet with included power supply, the usage of four cannel power distribution modules EP9214 or EP9224
(with integrated data logging, see www.beckhoff.com/EP9224) is recommended.

With these modules intelligent power distribution concepts with up to 2 x 16 A and a maximum of 2.5 mm²
cable cross­section can be realized.

EP9128

35