Installation – Desa VF-24N-BTB User Manual

Page 11

Advertising
background image

www.desatech.com

111826-01G

11

INSTALLATION

Continued

Figure 8 - Minimum Fireplace Clearances

If Installed at Floor Level

Figure 9 - Minimum Fireplace Clearances

Above Combustible Flooring

14"

Min.

Combustible

Material

Noncombustible

Material

Hearth

5"

Min.

Combustible

Material

MANTEL CLEARANCES

In addition to meeting noncombustible material

clearances, you must also meet required clearances

between fireplace openings and mantel shelf on

each side of the fireplace. If you do not meet the

clearances listed below, you will need a hood.
Determining Minimum Mantel Clearance

If you meet minimum clearance between mantel

shelf and top of fireplace opening, a hood is not

required (see Figure 6, page 10).
Determining Minimum Mantel Clearance
When using a Hood

If minimum clearances in Figure 6, page 10 are not

met, you must have a hood. When using a hood

there are still certain minimum mantel clearances

required. Follow minimum clearances shown in

Figure 7, page 10 when using hood.

NOTICE: Surface temperatures

of adjacent walls and mantels be-

come hot during operation. Walls

and mantels above the firebox

may become hot to the touch.

If installed properly, these tem-

peratures meet the requirement

of the national product standard.

Follow all minimum clearances

shown in this manual.

NOTICE: If your installation does

not meet the minimum clear-

ances shown, you must do one

of the following:

• operate the logs only with the

flue damper open

• raise the mantel to an accept-

able height

• remove the mantel

FLOOR CLEARANCES

A. If installing appliance on the floor level, you

must maintain the minimum distance of 14"

to combustibles (see Figure 8).

B. If combustible materials are less than 14" to

the fireplace, you must install appliance at

least 5" above the combustible flooring (see

Figure 9).

INSTALLING DAMPER CLAMP
ACCESSORY FOR vENTED
OPERATION

Note:

When used as a vented decorative appliance,

unit must be installed only in a solid fuel burning

fireplace with a working flue and constructed of

noncombustible material.

If your heater is a non-thermostatically-controlled

model, you may use this heater as a vented product.

There are three reasons for operating your heater

in the vented mode:

1. The fireplace does not meet the clearance

to combustibles requirements for vent-free

operation.

2. State or local codes do not permit vent-free

operation.

3. You prefer vented operation.

If reasons number 1 or 2 apply to you, you must

permanently open chimney flue damper. You must

install the damper clamp as accessory (to order

(see Accessories, page 25). This will insure vented

operation (see Figure 10, page 12). The damper

clamp will keep damper open. Installation instruc-

tions are included with clamp accessory.

See chart in Figure 10, page 12, for minimum

permanent flue opening will be maintained at

all times.

Advertising
This manual is related to the following products: